§ 32-122. Materials.  


Latest version.
  • Materials shall meet the following minimum specifications:

    (1)

    Concrete: 3000 psi cylinder strength at 28 days.

    (2)

    Concrete testing below 90 percent of this value shall be replaced.

    (3)

    Reinforcing steel: ASTM A615 (Grade 60 or 40.)

    (4)

    Concrete pipe for storm drainage: ASTM C76, Class III.

    (5)

    Water system pipe: Cement, AWWA C400, Class 150; PVC, AWWA C900, Class 200 (DR 14), gasketed joints.

    (6)

    Water system valves: AWWA C500.

    (7)

    Fire hydrants: AWWA C502, 2 hose, 1 pumper connection.

    (8)

    Sanitary sewer system pipe: Vitrified Clay ASTM C700 (plain end), PVC ASTM D1784 (Type 1, Grade 1), ASTM D-1869 joints, SDR 35 or thicker.

    (9)

    Water meter boxes: Concrete, cast iron or plastic.

    Other materials as specified by the developer and approved by the town.

(Ord. No. 1990-1, app. § 7, 4-16-1991)